Six remote code flaws were found in the Danfoss AK-SM800A supermarket fridge controller. These flaws let someone take control from far away in about an hour, said Midnight Blue researcher Carlo Meijer. The flaws are stack-based buffer overflows. They affect every firmware version up to and including 5.3.2, and no CVE numbers have been assigned yet.
Since October 11, cyber attacks have affected Danfoss and Copeland fridge controllers in Europe. Attackers began defrost cycles, causing losses of tens of millions of euros. Some stores had fires, says Wikipedia’s summary.
Who is behind the incidents is still debated. France has blamed Iran’s Shahid Kaveh unit, but SentinelOne says attribution remains open and the incidents may not share one operator. The French agency ANSSI also said its early findings pointed to exposed admin pages and weak passwords, not the older published bugs.
Meijer did not use fuzzing or AI. He downloaded the public firmware, ran the main program in an emulator, and looked for places where the code calls strcpy.
This old C function copies data without checking its size, so a long input can overflow memory. One unauthenticated web handler crashed after he sent a long string of “A” characters. He found at least five bugs of this kind in a small part of the code. The binary also lacked stack canaries and PIE, two basic protections that make such bugs harder to use. The program runs as root, so a successful exploit gives full control.
Supermarket Fridge Controller Takeover
Midnight Blue showed a way to exploit an older firmware version. The team is holding back details while it talks with Danfoss about sharing the information.
Danfoss included session control in newer firmware. The “strict” setting is the default from version 4.0. This setting stops most web attacks from users who aren’t logged in, and CERT-FR includes it in its official solutions.
The researchers found another overflow in sm_fcgi_app, the part that checks logins, and it still works on the newest firmware with strict mode on.
The team warns about what happens after a break-in. The controller does not use the secure boot features of the i.MX6 chip. An attacker with root access could add an implant that stays even after a factory reset.
They could erase the flash memory or add harmful software to ruin the device. This would make stores replace the equipment, and freezers could be unused for days. Midnight Blue compares this to the wiping methods used in the December 2025 attack on the Polish electric grid.
The researchers think fixing one bug at a time wastes staff time. Owners need to find all exposed controllers, even the ones behind integrators’ 4G modems. They should put remote access behind a VPN, a private APN, or a strict IP allow list. CERT-FR warns that allow lists are just a temporary solution.
Exposure is still high. Censys finds hundreds of Danfoss devices online, along with over 1,000 Copeland and Dixell units. Earlier news on Cyber Security talked about flaws in Copeland XWEB Pro, showing the same issue. Until these controllers are taken off the open internet, new problems will continue to endanger food and medicine.
Related news:
Multiple European supermarket fridges got hacked: Temperatures reached high as 55°C
InfoSecBulletin Cybersecurity for mankind